DELTA DVP Serisi PLC

Page 2

2

1. Haberlesme Arabirimi: RS-232C
2. Haberlesme protokolu ASCII mod, 9600(Baud rate), EVEN(Parity), 1

(Start bit),1(Stop bit)

3. DELTA PLC MODBUS PROTOKOL

4. Haberlesme Data Yapisi

STX Baslangic Karakteri ‘:’(3AH)
ADR 1 Haberlesme Adresi:
ADR 0 8-bit adres 2 ASCII kod icerir.
CMD 1 Komut kodu:
CMD 0 8-bit komutu 2 ASCII kod icerir.
DATA(0) Data Icerigi:
DATA(1) n×8-bit data 2n ASCII kod icerir.
………. n≤37, maksimum 74 ASCII kodu
DATA(n-1)
LRC CHK 1 LRC check sum:
LRC CHK 0 8-bit check sum 2 ASCII kod icerir
END 1 End karakter:
END 0 END 1 = CR(0DH),END 0 = LF(0AH)

ADR(Haberlesme Adresi)

Gecerli haberlesme adres araligi 0…31. Haberlesme Adresi `0` oldugunda

butun PLC'lerle haberlesme gerceklesir (broadcast) . PLC Master uniteye cevap

gonderir.

Ornegin, 16 no'lu PLC ile haberlesmek icin:

(ADR 1, ADR 0)=’1’,’0’ ’1’=31H, ‘0’ = 30H

CMD (Komut Kodu) ve DATA (data karakterleri)

Data karakterlerinin formati komut koduna baglidir. Ornegin, 01H no'lu PLC'nin

0614H adresinden itibaren 8 tane datayi okumak icin:

Alan Adi Ornek (Hex)

Baslangic (Heading) 3A
Slave Adres 01
Komut Kodu 03
Bas.Adresi (Yuksek) 06
Bas.Adresi (Dusuk) 14
Nokta Sayisi (Yuksek) 00
Nokta Sayisi (Dusuk) 08
Hata Kontrol ( LRC ) DA

Page 13

13

Komut Kodu :::17, Slave ID Raporu

Kontrol cihazinin slave adresi hakkinda RUN indikatoru hakkinda ve diger ozel

bilgiler verir.

Komut Mesaji:

Alan Adi Ornek (Hex)

Baslangic 3A
Slave Adres 01
Komut Kodu 11
Hata Kontrol (LRC) EE

Cevap Mesaji:

Alan Adi Ornek (Hex)

Baslangic 3A
Slave Adres 01
Komut Kodu 11
Byte Sayisi 04
Slave ID 01
Run Indikator Durumu
00 = OFF
FF = ON

FF

Data 0(D1001 HI ) 40
Data 1(D1001 LOW ) 10
Hata Kontrol (LRC) 9A