F133-P
DELIVERY / DISPENSE CONTROLLER








Signal input flowmeter: pulse, Namur and coil.

Status inputs: start and stop.

Control outputs: two pump / valve control outputs.

Options: Intrinsically Safe, Modbus communication and backlight.



F-Series - Field mounted indicators for safe and hazardous areas. More info: www.fluidwell.com/fseries

Page 2

HF133PEN_v0501_04

Page 2



SAFETY INSTRUCTIONS

Any responsibility is lapsed if the instructions and procedures as described in this

manual are not followed.

LIFE SUPPORT APPLICATIONS: The F133-P is not designed for use in life support

appliances, devices, or systems where malfunction of the product can reasonably be
expected to result in a personal injury. Customers using or selling these products for
use in such applications do so at their own risk and agree to fully indemnify the
manufacturer and supplier for any damages resulting from such improper use or sale.


Electro static discharge does inflict irreparable damage to electronics! Before installing

or opening the unit, the installer has to discharge himself by touching a well-grounded
object.


This unit must be installed in accordance with the EMC guidelines (Electro Magnetic

Compatibility).

Do connect a proper grounding to the aluminum casing as indicated if the F133-P has

been supplied with the 115-230V AC power-supply type PM. The green / yellow wire
between the back-casing and removable terminal-block may never be removed.


Intrinsically Safe applications: follow the instructions as mentioned in Chapter 5 and
consult “Fluidwell F1..-..-XI - Documentation for Intrinsic Safety”.





DISPOSAL
At the end of its life this product should be disposed of according to local regulations regarding
waste electronic equipment. If a battery is present in this product it should be disposed of
separately. The separate collection and recycling of your waste equipment will help to conserve
natural resources and ensure that it is recycled in a manner that protects the environment.





SAFETY RULES AND PRECAUTIONARY MEASURES

The manufacturer accepts no responsibility whatsoever if the following safety rules and

precautions instructions and the procedures as described in this manual are not followed.
Modifications of the F133-P implemented without preceding written consent from the

manufacturer, will result in the immediate termination of product liability and warranty period.
Installation, use, maintenance and servicing of this equipment must be carried out by authorized

technicians.
Check the mains voltage and information on the manufacturer's plate before installing the unit.
Check all connections, settings and technical specifications of the various peripheral devices

with the F133-P supplied.
Open the casing only if all leads are free of potential.
Never touch the electronic components (ESD sensitivity).
Never expose the system to heavier conditions than allowed according to the casing

classification (see manufacture's plate and chapter 4.2.).
If the operator detects errors or dangers, or disagrees with the safety precautions taken, then

inform the owner or principal responsible.
The local labor and safety laws and regulations must be adhered to.

Page 24

HF133PEN_v0501_04

Page 24

4.4.2. VOLTAGE SELECTION SENSOR SUPPLY

For Intrinsically Safe applications: read chapter 5.

Type PB / PC / PX (AP) - battery powered and output loop-powered applications:
Terminal 11 provides a limited supply voltage of 3.2 V DC (coil signals 1.2V) for the signal output of
the flowmeter.
Note: This voltage MAY NOT be used to power the flowmeters electronics, converters etc, as it will
not provide adequate sustained power ! All energy used by the flowmeters pick-up will directly
influence the battery life-time. It is strongly advised to use a "zero power" pickup such as a coil or
reed-switch when operating without external power. It is possible to use some low power NPN or
PNP output signals, but the battery life time will be significantly reduced (consult your distributor).

Type PD / PF / PM: Sensor supply: 1.2 - 3.2V - 8.2V - 12V or 24 V DC:
With this option, a real power supply for the sensor is available. The flowmeter can be powered with
8.2 - 12 or 24 V DC.
Total power consumption PD: max. [email protected] and PF / PM: max. [email protected]
The voltage is selected with the three switches inside the enclosure.


Warning: be sure that all the leads to the terminals are disconnected from the unit when

the internal plastic protection cover has been removed !
HIGH VOLTAGE 400V !! NEVER connect the mains power supply to the unit when the

plastic protection cover has been removed !!!

First, remove the terminal strip(s) after which the internal plastic cover can be removed. The
switches are located in the top left corner (type PD) or on the right hand (type PF / PM) as indicated:





Fig. 10: Switch setting sensor supply voltage.

Switch positions


SENSOR A SENSOR B VOLTAGE SELECTION
SWITCH 1 VOLTAGE SWITCH 2 VOLTAGE SWITCH 3 SWITCH 4 VOLTAGE
internal 3.2 V DC on on 8.2 V DC
external switch 3+4 on off 12 V DC

off off 23 V DC

Function switch 1: voltage selection sensor A - terminal 11.
Function switch 2: not available for this Model.
Function switch 3+4: the combination of these switches determine the voltage as indicated.

Do move switch 1 and / or switch 2 to the OFF position to enable the
selected voltage with switch 3+4.

Page 25

HF133PEN_v0501_04

Page 25

4.4.3. TERMINAL CONNECTORS


For Intrinsically Safe applications: read chapter 5.


The following terminal connectors are available:


7 8
R2

GND 31 4
N L1 R2

2

VALVE
OUTPUT R 2

TYPE
OA / OR / OT

9 10 11
+

12

STATUS
INPUT

1

65
R1 R1

16151413
SIGNAL

PUMP
OUTPUT R 1

TYPE
OA / OR / OT

STATUS
INPUT

2

+ SIGNAL

POWER SUPPLY
TYPE PX

POWER SUPPLY:
TYPE

PD / PF / PM

SENSOR SIGNAL
PULSE INPUT

TYPE P

SIGNAL



Fig. 11: Overview of terminal connectors standard configuration F133-P and options.




REMARKS: TERMINAL CONNECTORS:


REMARKS: TERMINAL CONNECTORS:

Terminal GND- 01- 02: Power Supply - only available with type PD / PF or PM:


TYPE SENSOR SUPPLY
Terminal

b
a

ck
lig

h
t

TY
P

E
A
A


TY

P
E
A

U
Ty

p
e

O
A


Ty

p
e

O
R



GND 01 02

PD 8-24V AC 8,2-12-24V max. 50mA AC AC ◊ ◊ ◊ ◊
PD 8-30V DC 8,2-12-24V max. 50mA L- L+ ◊ ◊ ◊ ◊
PF 24V AC ± 15% 8,2-12-24V max. 400mA AC AC ◊ ◊ ◊ ◊
PF 24V DC ± 15% 8,2-12-24V max. 400mA L- L+ ◊ ◊ ◊ ◊
PM 115-230V AC ± 15% 8,2-12-24V max. 400mA EARTH AC AC ◊ ◊ ◊ ◊ ◊

Note PD do not use a AC autotransformer (Spartrafo) without a galvanic isolation.
Note PF / PM The total consumption of the sensors and outputs may not exceed [email protected]

◊=option


Note: for power supply type PX: please read Terminal 07-08 !

Page 47

HF133PEN_v0501_04

Page 47



INDEX OF THIS MANUAL

accumulated Total 9
active output 26
actual settings 48
alarm delay time 15
analog

output loop powered. 27
Backlight 31
batch counter 9, 14
batch total 9, 14
battery life time 16, 37
begin time 18
Coil-signal 27
communication 31

family-specific variables 42
Configuration 10
control

begin time 18
delay time 18
no-pulse time 18
overrun time 18
pause 18
start-up time 18

cut off time 15
delay time 18
Dimension enclosures 21, 22
display update 16
external start / stop 19
flowmeter

signal 17
Flowmeter input 27
flowrate

alarm 9
calculation 15
decimals 15
decimals k-factor 15
k-factor 15
measuring unit 15
time unit 15

flowrate calculation 15
flowrate alarm 15
Installation 20
Intrinsic safety 32

Intrinsically Safe options 34
IP classification 20
keys 7
flowrate alarm 15
low-battery 9
main-function 11
maintenance 37
model 19
NAMUR-signal 29
no-pulse time 18
Operator level 8
overrun time 18
pass code 19, 41
pause 18
power supply 25
power supply intrinsically safe 34
Problem solving 41
Pulse-signal active pulse 29
Pulse-signal NPN/PNP 28
Reed-switch: 29
Relay output 26
restart time 18
serial number 19
SETUP-level 10
START 8, 19
Start, external input 30
start-up time 18
STOP 8, 19
Stop, external input 30
subfunction 11
tagnumber 19
Technical specification 38
terminal connectors 25
total

decimals k-factor 14
k-factor 14
max. batch size 14
measuring unit 14

Total 9
transistor output 26
version software 19
Voltage selection sensor 24

Page 48

HF133PEN_v0501_04

Page 48







LIST OF CONFIGURATION SETTINGS
SETTING DEFAULT DATE : DATE :



1 - TOTAL Enter your settings here
11 unit L
12 decimals 0000000
13 K-factor 0000001
14 decimals K-factor 0
15 max. batch size 0


2 - FLOWRATE
21 unit L
22 time unit /min
23 decimals 0000000
24 K-factor 0000001
25 decimals K-factor 0
26 calculation / pulses 010
27 cut-off time 30.0 sec.
28 low flowrate alarm 0.0 L/min
29 high flowrate alarm 0.0 L/min
2A alarm delay time 0.0 sec


3 - POWER MANAGEMENT
31 LCD-new 1 sec.
32 mode operational


4 - FLOWMETER
41 signal coil-lo


5 - RELAY OUTPUT
51 delay time 0.0 sec
52 begin time 0.0 sec
53 start-up time 0.0 sec
54 no pulse time 0.0 sec
55 pause disabled
56 restart time 0.0 sec
57 overrun time 0.0 sec


6 - STATUS INPUT
61 status input 1 off
62 status input 2 off


7 - COMMUNICATION
71 baud-rate 2400
72 address 1
73 mode BUS-ASC


8 - OTHERS
81 model F133-P F133-P F133-P
82 software version
83 serial number
84 pass code 0000
85 tagnumber 0000000